Jumat, 27 Maret 2009

Application Engineering Europe

POWER FACTOR CORRECTION


For many years electric utilities and large industrial plants have reduced electrical current demands by the use of capacitors to increase the power factor on large electrical loads. With the growing emphasis on the need to conserve electrical energy, there is increasing interest in power factor correction for three-phase motors, even on small installations.

1 Electrical Fundamentals
The study of electrical engineering theory is extremely complex. Fortunately, the practical application of electricity involves exact scientific relationships that follow precise physical laws, so the application engineer needs be concerned only with basic formulas and relationships.
To understand power factor, a review of electrical fundamentals may be helpful.
Volt is the electrical unit of measurement used to express the electrical potential or force which causes current flow.

Ampere is the term used to express the rate of electrical flow or current.
Watt is used to express the power consumed.
Ohm is used to express the resistance to flow of current in a circuit.
In alternating current systems, both voltage and amperage rise and fall thru cycles such as illustrated schematically in Figures 1 and 2. The number of cycles per second is referred to as the frequency (hertz).

The values which we measure for voltage and amperage in a circuit are actually mean values occurring during the cycle.

If the voltage and amperage are in phase, as in Figure 3, the power consumed (watts) is equal to the product of the volts times amps. If, however, the voltage and amperage are out of phase, as in Figure 4, the product of volts times amps is only “apparent power” (volt-amperes), and the actual power (watts) is some lesser value, the reduction being determined by the degree to which current and voltage are out of phase.

Power factor is defined as the ratio of the power consumed doing work (watts) divided by the apparent power (volts-amperes). In direct current circuits, since there is no reversal of voltage or current, the power factor in effect is always unity. In alternating current circuits with lagging current (caused by inductive loads), the actual power available for work is the product of the volts times amperes times the power factor.

2 Electrical Formulas
The following basic formulas govern the relationship of voltage, amperage, and power in electrical circuits.




3 Apparent Power and Actual Power
The mathematical relationship between actual power and apparent power is shown by means of a vector diagram, Figure 5. The line AB is the reference point for voltage and measures the actual power. If the current is in phase with the voltage, then the apparent power is equal to the actual power, and the power factor is 1.0. This would be true of circuits with only resistive loads, such as electric heaters.

All inductive devices, such as motors, transformers, and solenoid coils require magnetizing current to create the magnetic field necessary for the device to operate. This magnetizing current, or reactive current as it is termed, does not produce usable power, but the effect of the magnetic field is to cause the current drawn from the power line to lag the voltage. The term reactive power is used to describe the product of the reactive current and the operating voltage, and is measured by line BC. The greater the reactive current, in proportion to the useful current, the greater the reactive power and the lower the power factor. The apparent power (volt-amperes) is measured by line AC. The symbol θ (theta) is conventionally used to denote the power factor angle.

Capacitors have a directly opposite effect to inductive magnetizing current and cause the current to lead the voltage rather than lag. As a result, capacitors installed in circuits with low power factors tend to cancel the effects of the reactive current and increase the power factor.

3.1 Effect of Poor Power Factor
Regardless of the actual power consumed, the electric distribution system sees volt-amperes. The presence of reactive current means the power supply lines must carry more current than that actually consumed by the load, and this additional current causes greater line losses, more voltage drop, and imposes a greater load on generators, transformers
and distribution lines.

Generator and transformer output is measured in volt-amperes, so the greater the reactive current, the less actual (or usable) power the generator can produce and the transformer can handle. The combined effects of low power factor greatly increase the power company’s cost for capital equipment, so power companies frequently charge penalties for low power factors.
The reasons for this are that power companies must be prepared to satisfy normal transmission line (I2R) losses caused by low power factor and also increase generating capacity to provide apparent power. As energy production costs rise and energy conservation becomes more important, it is probable that electrical specifications will increasingly call for power factor correction.

3.2 Calculating Power Factor Correction
The vector power diagram provides a convenient means of mathematically calculating power factor correction. Figure 6 diagrams an actual motor installation.
The metric prefix “k” for kilo means 1000, so the actual power is 12 kW and the apparent power is 15 kVA.
The power factor by definition is actual power divided by apparent power, and is equal to .80.
To determine the reactive power, it is necessary to calculate a leg of the power factor triangle. As you will recall, the square of the hypotenuse (side opposite the right angle) is equal to the sum of the squares of the other two sides.

Therefore,
(AC)² = (AB)² + (BC)²
(BC)² = (AC)² - (AB)²
(Reactive Power)² = (15)² - (12)²
Reactive Power = √(225-144) = √81 = 9 kVAR

A kilovar (kVAR) is 1000 volt-amperes of reactive power. If sufficient capacitance is added to the circuit to produce 9 kVAR of leading reactive power, this will cancel the 9 kVAR of lagging reactive power created by the induction motor; the apparent power and actual power will become the same; and the power factor will be increased to 1.0.

3.2.1 Electric Motor Characteristics
Figure 7 shows the motor performance curves for a typical three-phase induction motor. The only scales shown are for power factor and motor torque, but the remainder of the curves are shown for reference. All values other than torque are on a vertical scale.
Note that even with no load, and no power consumption, the motor continues to draw magnetizing current. Since this reactive magnetizing current is relatively constant, the power factor declines rapidly as the motor loading is reduced.

3.2.2 Dangers of Over-Correction
It is always possible to correct a motor to unity power factor, but total correction is normally not recommended. The influence of other reactive forces on the power line, such as changing motor or transformer load, is unpredictable, and if the power factor is over-corrected, it can cause high currents, high magnetic side pull forces on the motor rotor, high voltage, and transient motor over-torque much greater than full load motor torque. Whether overcorrection will cause motor damage is uncertain, but there is evidence that motor life can be shortened by voltage spikes caused by over-correction. A safer course is a more conservative one, limiting correction to the .9 (or 90%) level.

3.2.3 Calculating Kilovars of Power Factor Correction for Three-Phase Motors
Convenient tables of power factor correction factors have been calculated to avoid the necessity for a laborious calculation for each application. Table 1 gives multipliers to be used to determine the capacitor kilovars required. The multiplier (or KK) to be used is found by locating the original power factor in the left hand column, and then reading the required value at the intersection of the original power factor row, and the desired corrected power factor. The required kilovars are then calculated as follows:

kVAR = (KK) x (kW load)

The original compressor power factor can easily be calculated from the compressor specification sheet.
The equation for three-phase power (from page 1) is:

Power (Watts) = UI cos φ √3
Therefore, power factor can be calculated by:
cos φ = P/ (UI√3)

Example:
Determine the kilovar correction necessary to increase the power factor to 90% for a ZR16K3E-TWD, 400 V, 50 Hz,, high temperature compressor operating at ARi Point (evap = 7.7°C cond = 54.4).

a) From a typical specification sheet, the compressor power input is 11400 Watt and the amperage draw is 19.12 Amps

b) cos φ = P/ (UI√3) = 11400/(400 x 19.12 x 1.73) =0.86
c) From table 1, the required multiplier, or KK, is 0.109
d) KVAR correction = 0.109 x 11400 = 1.24 kVAR

A similar equation from page 1 may be used to determine single-phase kVAR. For any given application, the kilovars required for power factor correction are determined by the operating condition selected as a basis for correction and the amount of correction desired.
The power factor and correction required can vary greatly when the compressor operates outside of ARI conditions.

Senin, 16 Februari 2009

ALAT PENAMBAH DAYA LISTRIK

BOLEH PERCAYA, BOLEH TIDAK!!!!!
BISA DIPIKIRKAN ATAU DIANALISA SENDIRI!!!!

ALAT PENAMBAH DAYA LISTRIK
TANPA MERUBAH ATAU MENGGANGGU
INSTALASI PLN (KWH DAN MCB)



Rumah Anda dengan Kapasitas 4A/22o V dengan Kemampuan 4A x 220Volt = 880 Watt (VA) yang efektif Daya gunannya = 4A x 220V x 0.8 = 704 Watt(VA), dapat menggunakan Peralatan listrik dengan Daya (VA/Watt), lebih dari 6A x 220V = 1320 Watt (VA)

TANPA MERUBAH INSTALASI LISTRI PLN ANDA!!!!,
LEGAL bukan PENCURIAN LISTRIK!!!!,
MUDAH MENGGUNAKANNYA !!!!!!


TANPA MERUBAH INSTALASI LISTRI PLN ANDA!!!!
YA!!!!,Tanpa merubah Instalasi Listrik PLN ANDA, Karena Alat ini mudah cara penggunaannya hanya dengan memasang di STOP KONTAK dimana Anda inginkan menambah DAYA LISTRIK ANDA, berarti TIDAK Mengganggu Jaringan Instalasi Listrik ANDA dan Dipasang setelah Jaringan LISTRIK PLN.

Peralatan yang akan ditambah tinggal Memasangnya setelah Alat ini

LEGAL bukan PENCURIAN LISTRIK!!!!,
YA!!!, Karena Alat ini dipasang pada STOP KONTAK dimana beban yang Lebih kita inginkan SETELAH KWH METER LISTRIK PLN dan MCB (Pembatas Listrik PLN) tanpa MENGGAGU JARINGAN LISTRIK PLN dan SEGEL METER PLN

MUDAH MENGGUNAKANNYA !!!!!!
YA!!!!, Hanya memasang ALAT ini Pada setiap STOP KONTAK yang anda inginkan dan Pasangkan Beban Listrik yang anda inginkan pada ALAT ini

APA KEUNTUNGAN YANG ANDA DAPATKAN???

  1. Keuntungan yang ANDA dapatkan adalah Anda Tidak perlu Mengeluarkan BIAYA untuk Menambah BEBAN LISTRIK, Anda Tidak perlu Mengeluarkan Biaya Tambahan setiap Bulannya untuk BIAYA Langganan dan BEBAN Listrik dan Anda tidak Perlu lagi Buang Waktu untuk Pengurusan semua itu.
  2. Seluruh BEBAN Listrik ANDA setelah Alat ini DAYA BEBAN TERPAKAI (WATT/VA) = DAYA BEBAN DIBAYAR, atau dengan istilah Teknik keListrikan KVAR>= 0, COS θ (Theta/PI) = 0.99
  3. Dengan Kata Lain BEBAN LISTRIK ANDA Bertambah, Biaya Listrik Anda Berkurang, HEMAT UANG, HEMAT ENERGI

BERAPA MACAM TIPE ALAT INI?

SINGLE PHASE/ 1 PHASE
ALAT UNTUK 4A/220v (TIPE 880WATT), DAYA DIPAKAI 1400 WATT
ALAT UNTUK 6A/220v (TIPE 1320WATT), DAYA DIPAKAI 2500 WATT
ALAT UNTUK 10A/220v (TIPE 2200WATT), DAYA DIPAKAI 4000 WATT
ALAT UNTUK 15A/220v (TIPE 3300WATT), DAYA DIPAKAI 6000 WATT
ALAT UNTUK 20A/220v (TIPE 4400WATT), DAYA DIPAKAI 8000 WATT

3 PHASE
ALAT UNTUK 3 X 10A/220v (TIPE 3 X 2200WATT) = 6600 WATT,
DAYA DIPAKAI 12000 WATT

BERAPA BIAYA ALAT TERSEBUT ??
Biaya Alat adalah DAYA DIPAKAI per WATT/VA = Rp. 1000,-, Sangat Murah dan Terjangkau, jadi jika ALat untuk 4A/220 V = 880 VA(WATT), DAYA DIPAKAI adalah 1400 WATT(VA) dikalikan Rp.1000,- Harga ALat tersebut Rp. 1.400.000,-

DIMANA DAPAT MEMBELI ALAT INI???
Alat ini Tidak diproduksi dan dijual Dimanapun, Alat ini Hanya ANDA dapat peroleh dengan menghubungi Kami disini atau di sini, ALAT INI HANYA BISA DIPESAN (INDENT) !!!!!

MOTTO KAMI ADALAH:
BEKERJA BERDASARKAN KEPERCAYAAN DAN KOMITMENT
KAMI SERING DI TIPU TAPI KAMI TIDAK MAU MENIPU!!

JIKA ANDA INGINKAN HAK CIPTA
DAN
HAK PAKAI ALAT INI


HUBUNGI KAMI DISINI


KAMI YANG PERTAMA
DAN
KAMI BERIKAN YANG TERBAIK UNTUK ANDA